| Connection |
Can be connected via RJ-11 cable to each control unit. Determination of the sensor type and connection takes place automatically. At the end of the sensor, connect the 2-wire VT-WLC detection cable. |
|---|---|
| Maximum distance from the controller | 100m |
| The maximum length of the detection cable track | 225m |
| Set includes |
sensor, cable, terminal strip type TBW-5-2p, screw 4.8×16mm, double sided sticker, VT-WLC adapter |
| Net weight | 60g |
| Dimensions (LHW) | 60×18×18mm |
| Connection | The sensor is connected to the controller by the RJ-11 network cable. Determination of the sensor type and connection takes place automatically. Sensor response time 0.1s |
|---|---|
| Max. distance | 50m |
| Net weight | 106g |
| Dimensions | 60×18×18mm |
| Power Consumption | 60mW |
| Supply includes |
Sensor converter, airflow sensor, mounting bracket, 2m RJ11/RJ12 cable, screws, nuts, bolts and a sticker. |
| Technical specifications | |
|---|---|
| Measured temperature range | -10 ÷ 80°C |
| Accuracy | ±0.4°C in –10 to 85 °C range |
| Measured humidity range | 0 - 95%RH |
| Accuracy %RH | ± 3% RH in 0 to 80% range |
| Maximum distance from the appliance | 225m |
| Features | |
| Connection |
Sensor's jack RJ-12 is connected to CAN input of any system unit or to a CAN output of another sensor using RJ-12 patch cable. Determination of sensor's type and connection occur automatically. The system enables connecting multiple sensors to a linear layout. For this purpose, each sensor is equipped with two RJ-12 input and output sockets. |
| Net weight | 160g |
| Dimensions | 68 × 47 x 26 mm |
| Communications | |
|---|---|
| Sesnor type | CAN digital sensor |
| Inputs/Outputs | 2x RJ11 6p4c |
| Daisy chain |
Yes, a daisy chain is possible for all CAN sensors. |
| Max. distance from the monitoring unit | 225m |
| LED indicators | Red / Green (RUN/ERROR) |
| Accuracy | |
| Pressure RMS noise | 0.2Pa (equivalent to 1.7cm) |
| Pressure error | ±0.25% (equivalent to 1m at 400m height change) |
| Pressure from °C | ±1.5Pa/K (equivalent to ±12.6cm at 1 °C temperature change) |
| RH accuracy | ± 3% RH (max) |
| Hysteresis | ≤2% RH |
| Response time | 1s |
| Temperature | 1.5°C |
| Environmental | |
| Pressure range | 300 to 1100 hPa |
| Working temperature range | −40 to +85 °С |
| Humidity operating range | 0 to 95% RH |
| Power Requirement | |
| Power input |
12V DC, 1A (power supplied on a CAN bus chain) |
| Current consumption | 1 Watt |
| Mechanics | |
| Dimensions | 68x47x26 mm |
| Packaging weight | 160 g |
| Technical specifications | |
|---|---|
| Smoke sensitivity | 0,05 - 0,2 db/m |
| Response time | 10 sec |
| Measured temperature range | -10 to +75 °C |
| Accuracy | ±0.4°C in –10 to 85 °C range. |
| Measured humidity range | 0 - 95%. |
| Accuracy %RH | ± 3% RH in range of 0 - 80% |
| Maximum distance from the appliance | 225m |
| Features | |
| Installation | On the bottom there are mounting holes for fastening the smoke sensor to the surface using screws 4.8×20mm or/and bracket and M4 screws. |
| Connection | Sensor's jack RJ-12 is connected to CAN input of any system unit or to a CAN output of another sensor using RJ-11 patch cable. Determination of sensor's type and connection occur automatically. Monitoring system allows connection of up to 40 smoke sensors into a linear circuit. |
| Set includes |
Sensor, 3-wired shielded patch cable RJ12 (2m), bracket, 2 screws and 2 nuts M4, 2 screws 4.8×20mm, double sided sticker. |
| Net weight | 310g |
| Dimensions (LHW) | Ø100×45mm |
| Connection: | |
|---|---|
| Power input | -12V / +12V |
| Outputs | 4 pin terminal |
| Power Consumption | 1 Watt |
| Operating temperature | -10°C ÷ 80°C |
| Operating humidity |
5% ÷ 95%, non-condensing |
| Net weight | 150g |
| Dimensions (LHW) | 68 × 47 x 26 mm / 60 × 61 × 16 mm |
| Technical specifications | |
|---|---|
| Rated voltage | 12V |
| Sound pressure | 108 dB |
| Tone frequency | 3.8 kHz |
| Flash frequency | 150 / min |
| Net weight | 140g |
| Dimensions (LHW) | 70 x 36 x 56 mm |
| Technical specifications | |
|---|---|
| Rated voltage | 12V |
| Flash frequency | 90 / min |
| Net weight | 110g |
| Dimensions (LHW) |
73 x 45mm, cable 3m |
| Technical specifications | |
|---|---|
| Type | Power supply for CAN bus chain |
| Input | RJ11 6P4C CAN port ⌀3.4/1,35 mm 12V |
| Otuput | RJ11 6P4C CAN port |
| Daisy chain | Allows daisy chain |
| Max. q-ty of CAN sensors powered | 15 |
| LED indicators | Green (Status On/Off) |
| Environmental | |
| Working temperature range | −40 °C to +100 °C |
| Humidity operating range | 0-95% RH |
| Mechanics | |
| Dimensions | 68 x 67 x 26,2 mm (LxWxH) |
| Packaging weight | 190g |
| Mounting options |
Desktop, Wall mount, Indoor |
Page 3 of 6
|