Atel Electronics
[-]remove#08396
Power supply 120W 24VDC, DIN TS35, P.F.C. (Mean Well SDR-120-24)
Environment
Working temperature -25°C ÷ 70°C
Working humidity 20÷95% RH non-condensing
Storage temperature -40°C ÷ 85°C
Storage Humidity 10÷95% RH
Temperature coefficient ±0.03%/°C (0÷50°C)
Vibration (component) 10÷500Hz,
2G 10min./1cycle,
60min. each along X Y Z axes
Vibration (mounting) compliance to IEC60068-2-6
Input
Voltage range 88÷264VAC,
124÷370VDC
Frequency range 47÷63Hz
Power factor (typ.) 0.93/230VAC at full load,
0.96/115VAC at full load
Efficiency (typ.) 91%
AC current (typ.) 1.4A/115VAC,
0.7A/230VAC
Inrush current (typ.) 35A/115VAC cold start,
70A/230VAC cold start
Leakage current <1mA/240VAC
Others
MTBF min. 289900h MIL-HDBK-217F (25°C)
Dimension (W x H x D) 40mm x 125,2mm x 113,5mm
Weight 0,67kg
Output
DC Voltage 24V
Rated current 5A
Current Range 0÷5A
Rated Power 120W
Ripple & noise (max.) 100mVp-p
Voltage adjustment range 24÷28V
Voltage tolerance ±1.0%
Line regulation ±0.5%
Load regulation ±1.0%
Setup & rise time 1500ms & 60ms/230VAC at full load,
3000ms & 40ms/115VAC at full load
Hold up time (typ.) 20ms/230VAC at full load,
20ms/115VAC at full load
Protection
Overload 110%÷150% rated output power,
protection type - constant current limiting - recovers automatically after fault condition is removed
Overvoltage 29÷33V,
protection type - shut down o/p voltage & re-power on to recover
Over temperature 95°C ±5°C (TSW1) detect on heatsink of power transistor,
protection type - shut down o/p voltage & re-power on to recover
Safety & EMC
Safety standards UL508,
UL60950-1,
TUV EN60950-1
Withstand voltage I/P-O/P 3kVAC,
I/P-FG 1.5kVAC,
O/P-FG 0.5kVAC
Isolation resistance I/P-O/P 100MΩ/500VDC,
I/P-FG 100MΩ/500VDC,
O/P-FG 100MΩ/500VDC
EMI conduction & radiation EN55011,
EN55022 (CISPR22),
EN61204-3 Class B
Harmonic current EN61000-3-2,
EN61000-3-3
EMS immunity EN61000-4-2/3/4/5/6/8/11,
ENV50204,
EN55024,
EN61000-6-2 (EN50082-2),
heavy industry level criteria A
Net Price 58.50 USD